INT301 INT302® Temperature monitor for Pt100 or Pt1000 sensors KRIWAN

INT301 INT302® Temperature monitor for Pt100 or Pt1000 sensors KRIWAN

INT301/INT302® Temperature monitor for Pt100 or Pt1000 sensors
KRIWAN
12 14 11
22 24 21
32 34 31
1 2 3 4 5 6
89 10
out/in
ZA Phi / 4
51 52 53
1 2 3 4 5 6 7 8 9 10
out/in 0/4 20mA
AC/DC 24V
51 52 53
INT30x Temp. monitor
without galvanically isolated analogue output
with galvanically isolated analogue output
Connection diagram
Application:
motors
pumps
Functional description:
The INT30x devices can be pro-grammed to operate in two ways.
Mode 1: An output relay is allo-cated to each sensor, the switching point can be individu-ally set for each sensor.
Mode 2: The relays are allocated warning, trip and alarm functions
Special features:
easy 2-key operation
analogue input
analogue output (option: gal vanically isolated)
variable hysteresis
password access possible
All inputs are designed for low voltage - do not con-nect to mains voltage. We rec-
Technical data
Supply
Ambient temperature range
Measuring range
Accuracy
Temperature sensor (2-lead)
Relay (3x change-over)
Mechanical service life
Analogue output
transformers
gears/bearings
common to all three sensors and to the analogue input. The alarm and trip points can be set individually for each sensor and for the analogue input. The alarm relay signals sensor open or short circuit.
3 monitoring circuits in one
device
easy lead compensation
cascade configuration possible
Intelligent response to sensor
faults
ommend to shield the sensor cables and to ground unilater-ally at the switching cabinet.
AC/DC 50/60Hz 24V plus/minus 1096 3
-20... 60 deg * C
-50... 250 deg * C resolution 1K)
(plus/minus 1)% of measuring range)
Pt100/Pt1000 acc. to EN 60751
AC 250V, max. 6A ohmic,
3A inductive, 300VA inductive approx. 1 mio, switching cycles
0(4)...20mA, active, burden <= 500Omega
4...20mA, passive
Analogue input
Screw terminals
Housing
ABS
Protection class acc, to EN 60529
Mounting
Dimensions
Weight
front mounted: IP65 (built-in)
housing:
IP20
front panel mounting
approx. 130g
74 * 34 * 85mm
0000000000
71
Cut-out: 71 * 29mm
Dimensions in mm
Ordering information
INT301 for Pt100 sensors
INT301 with galvanically
Isolated analogue output
INT302 for Pt1000 sensors
INT302 with galvanically.
isolated analogue output
Transformer AC 50/60Hz
230V 3VA
Transformer AC 50/60Hz
115V 3VA
20 A 501
20 A 501 $21
20 A 502
20 A 502 S21
CD4200153F